EH/0S

Vent Cap, End-of-Line 

Features

Cost Effective Device
Cost Effective Device
Vent Cap Provides Protection
Against Environmental Impact (Harsh Weather Conditions, Bird Nests, etc.)
Prácticamente libre de mantenimiento
Almost Maintenance Free
Certified Flow Performance Curves
Certified Flow Performance Curves
Function and Description

Weather Protection Hood for Efficient Ventilation

The Pressure/vacuum relief valve Pressure/vacuum relief valve is an umbrella term that includes pressure or vacuum relief valve as well as pressure and vacuum relief valve. PROTEGO® EH/0S vent cap Vent cap End-of-line device for free out-breathing and in-breathing of plant components. This device can be flame transmission-proof. allows vessels which are not pressurized to vent. This device Device A device is a pipe component that influences the media flow by opening, closing, or partially shutting off the flow channel or by dividing or mixing the media flow. prevents rain and dirt entering the vent line. The PROTEGO® EH/0S vent cap is not flame transmission proof. It is often used in combination with Detonation Detonation Explosion propagating at supersonic velocity and characterized by a shock wave (EN 1127-1: 1997). Flame Arresters Flame arrester Device fitted to the opening of an enclosure, or to the connecting pipe work of a system of enclosures, and whose intended function is to allow flow but prevent the transmission of a flame. , when those are used in vent lines, installed at a position which creates a long run up distance from the end of the vent line to prevent endurance burning Endurance burning Stabilized burning for an unlimited time. . The PROTEGO® EH/0S will then be installed at the end of that vent line to prevent particles or rain from entering the line. The vent cap PROTEGO® EH/0S main components are a housing Housing A housing is a solid shell, which surrounds a content, either protecting the content from external influences, or protecting the environment from the content. (1), a weather hood Weather hood A weather hood is a cover to protect the internal components of a device from environmental influences. (2) and a protection screen (3). The device is equipped with a fixed weather hood out of metal. The protection screen prevents particles or rain from entering the line.
Product Data

Dimensiones

To select the nominal size Nominal size The nominal size is an alphanumeric designation of size for components in a piping system, used for reference purposes, comprising the letters DN followed by a dimensionless integer that is indirectly related to the physical size of the bore or outside diameter of the connections, expessed in millimeters. (DN), please use the flow capacity charts on the following pages

DN100 / 4" 150 / 6"200 / 8"250 / 10"300 / 12"350 / 14"400 / 16"500 / 20"600 / 24"
a295 / 11.61550 / 21.65550 / 21.65600 / 23.62600 / 23.62600 / 23.62650 / 25.59800 / 31.501000 / 39.37
b230 / 9.06240 / 9.45240 / 9.45325 / 12.80320 / 12.60335 / 13.19370 / 14.57385 / 15.16520 / 20.47

Dimensiones en mm / pulgadas

Selección de materiales

Design AB
HousingSteelStainless Steel
Weather hoodStainless SteelStainless Steel

Special materials upon request

Tipo de bridas de conexión

EN 1092-1; Form B1
ASME B16.5 CL 150 R.F.

other types upon request

Diagrama de flujo volumétrico

Los diagramas de flujo volumétrico han sido determinados con un banco de pruebas de caudal calibrado y certifi - cado por TÜV. El flujo volumétrico V. en [m³/h] y el CFH se refi eren a las condiciones estándar de referencia de aire según ISO 6358 (20°C, 1bar). La conversión a otras densidades y temperaturas están referidas en el Vol. 1: “Fundamentos Técnicos”.

Applications

Instalaciones de procesamiento

Sistemas de combustión por vapor

Tanques de almacenamiento

Depósitos para el almacenamiento de alcohol

Si tienes alguna pregunta, comentario o sugerencia, nuestro equipo de expertos estará encantado de ayudarte.