P/EL

Pressure Relief Valve

Function and Description

10% Technology

The device will start to open as soon as the set pressure is reached and only requires 10% overpressure to full lift. Continuous investments into research and development have allowed PROTEGO® to develop a low pressure valve which has the same opening characteristic as a high pressure safety relief valve. This “full lift type” technology allows the valve to be set just 10% below the maximum allowable working pressure of the tank and still safely vent the required mass flow.

Highly Developed Manufacturing Technology

Due to our highly developed manufacturing technology the tank pressure Tank pressure Tank pressure is the pressure within a tank. is maintained up to set pressure, with a tightness that is far superior to the conventional standard. This feature is achieved by valve seats made of high quality stainless steel and with precisely lapped valve pallets (1) or with an air cushion seal Seal A seal prevents or limits unwanted transfer of product from one container to another. Seal is used as superordinate term for all types of sealing elements. (2) in conjunction with high quality FEP diaphragm Diaphragm A diaphragm is a thin layer of material, which has a large surface area. . The valve pallets are also available with a PTFE seal to prevent the valve pallets from sticking when sticky products are used, and they enable the use of corrosive media. After the excess pressure is discharged, the valve reseats and provides a tight seal. The optimized fluid dynamic design of the valve body and valve pallet is a result of many years of research, resulting in stable operation of the valve pallet, optimized performance, and reduced product losses.
Product Data and Features

Dimensiones

To select the nominal size Nominal size The nominal size is an alphanumeric designation of size for components in a piping system, used for reference purposes, comprising the letters DN followed by a dimensionless integer that is indirectly related to the physical size of the bore or outside diameter of the connections, expessed in millimeters. (DN), use the flow capacity chart on the following page

DN50 / 2" 50 / 2" 80 / 3" 80 / 3"
Set pressure≤ +80 mbar> +80 mbar≤ +80 mbar> +80 mbar
Set pressure≤ +32.1 inch W.C.> +32.1 inch W.C.≤ +32.1 inch W.C.> +32.1 inch W.C.
a218 / 8.58218 / 8.58218 / 8.58218 / 8.58
b287 / 11.30452 / 17.80289 / 11.38454 / 17.87

Dimensiones en mm / pulgadas

Dimensions for pressure valves with heating jacket upon request

Selección de materiales para la vivienda

DesignBC
HousingSteelStainless Steel
Heating jacket
(P / EL-H-...)
SteelStainless Steel
Valve seat Valve seat The valve seat is a component on which the valve pallet rests when the valve is closed. Stainless SteelStainless Steel
Weather hood Weather hood A weather hood is a cover to protect the internal components of a device from environmental influences. SteelStainless Steel
Protective mesh screenStainless SteelStainless Steel

Special materials upon request

Selección de materiales para la válvula de presión

Design ABCD
Pressure range [mbar]
[inch W.C.]
+3,5 up to +5,0
+1.4 up to +2.0
>+5,0 up to +14
>+1.4 up to 5.6
>+14 up to +210
>+5.6 up to +84
>+14 up to +210
>+5.6 up to +84
Valve palletAluminiumStainless SteelStainless SteelStainless Steel
SealingFEPFEPMetal to MetalPTFE

Special materials(Aluminium-coated, Titanium, Hastelloy) and higher pressure Settings upon request

Tipo de bridas de conexión

EN 1092-1; Form B1
ASME B16.5 CL 150 R.F.

other types upon request

Modelo y especificación

The valve pallet is weight-loaded. At set pressures greater than 80 mbar (32.1 inch W.C.), an elongated construction is used.
There are two different designs:
Pressure valve in basic designP/EL - –
Pressure valve with heating jacketP/EL - H

Additional special devices available upon request.

Settings

Pressure:+3.5 mbar+210 mbar
+1.4 inch W.C.+84 inch W.C.

Higher pressure settings upon request.

Diagrama de flujo volumétrico

Los diagramas de flujo volumétrico han sido determinados con un banco de pruebas de caudal calibrado y certifi - cado por TÜV. El flujo volumétrico V. en [m³/h] y el CFH se refi eren a las condiciones estándar de referencia de aire según ISO 6358 (20°C, 1bar). La conversión a otras densidades y temperaturas están referidas en el Vol. 1: “Fundamentos Técnicos”.

Detail X

Detail X

Applications