PV/EBR
Pressure/Vacuum Relief Valvedeflagration- and endurance burning-proof

Features
Extreme Tightness
Optimum Pressure Maintenance
Guided Valve Pallet
Protective System According to ATEX
Safety Against Endurance Burning
Lifting Device
Modular Design
Intergrated Flame Arrester

combined pressure and vacuum relief valve

For Explosion groups IIA to IIB3

advanced manufacturing technology

Main component - PROTEGO® flame arrester

Many Individual Certifications
Dimensiones
To select the nominal size Nominal size The nominal size is an alphanumeric designation of size for components in a piping system, used for reference purposes, comprising the letters DN followed by a dimensionless integer that is indirectly related to the physical size of the bore or outside diameter of the connections, expessed in millimeters. (DN), please use the flow capacity charts on the following pages
Dimensiones en mm / pulgadas
Dimensions for pressure/ vacuum relief valve with heating jacket upon request
Selección del grupo de explosión
| MESG | Expl. Gr. (IEC / CEN) | Gas Group (NEC) |
| > 0,90 mm | IIA | D |
| ≥ 0,65 mm | IIB3 | C |
Special approvals upon request
Tipo de bridas de conexión
| EN 1092-1; Form B1 |
| ASME B16.5 CL 150 R.F. |
other types upon request
Modelo y especificación
Almost any combination of vacuum and pressure levels can be set for the valve. The valve discs are weight loaded. When the difference between the pressure and vacuum exceeds 150 mbar / 60.2 inch W.C., special valve discs are used.There are two different designs:
Additional special devices available upon request
Settings
| Pressure: | +2.0 mbar | +210 mbar |
| +0.8 inch W.C. | +84 inch W.C. | |
| Vacuum: | -14 mbar | -50 mbar |
| -5.6 inch W.C. | -20 inch W.C. | |
| Vacuum: | -3.5 mbar | -14 mbar |
| -1.4 inch W.C. | -5.6 inch W.C. |
for presssure up to max. + 150 mbar / 60.2 inch W.C.
Higher and lower settings upon request
Selección de materiales para la vivienda
| Design | B | C |
| Housing | Steel | Stainless Steel |
| Heating jacket (PV / EBR-H-...) | Steel | Stainless Steel |
| Valve seat Valve seat The valve seat is a component on which the valve pallet rests when the valve is closed. | Stainless Steel | Stainless Steel |
| Weather hood | Steel | Stainless Steel |
Special materials upon request
Combinación de materiales para la unidad apagallamas
| Design | A |
| FLAMEFILTER® cage | Stainless Steel |
| FLAMEFILTER® | Stainless Steel |
| Spacer Spacer The spacer is a component that is generally used in a PROTEGO® flame arrester as a spacer within the FLAMEFILTER® se | Stainless Steel |
Special materials upon request
Selección de materiales para la válvula de presión
| Design | A | B | C | D |
| Presure range [mbar] [inch W.C.] | +2,0 up to +3,5 +0.8 up to 1.4 | >+3,5 up to +14 >+1.4 up to +5.6 | >+14 up to +210 >+5.6 up to +84 | >+35 up to +210 >+14 up to 84 |
| Valve pallet | Aluminium | Stainless Steel | Stainless Steel | Stainless Steel |
| Sealing | FEP | FEP | Metal to Metal | PTFE |
Special material as well as higher set pressure upon request
Selección de materiales para la válvula de vacío
| Design | A | B | C | D |
| Vacuum range [mbar] [inch W.C.] | -3.5 up to -5.0 -1.4 up to -2.0 | <-5.0 up to -14 <-2.0 up to -5.6 | <-14 up to -50 <-5.6 up to -20 | <-14 up to -50 <-5.6 up to -20 |
| Valve pallet | Aluminium | Stainless Steel | Stainless Steel | Stainless Steel |
| Sealing | FEP | FEP | Metal to Metal | PTFE |
Special material as well as higher set vacuum Set vacuum Internal negative gauge pressure at which a vacuum valve first opens. upon request
Diagrama de flujo volumétrico




Los diagramas de flujo volumétrico han sido determinados con un banco de pruebas de caudal calibrado y certifi - cado por TÜV. El flujo volumétrico V. en [m³/h] y el CFH se refi eren a las condiciones estándar de referencia de aire según ISO 6358 (20°C, 1bar). La conversión a otras densidades y temperaturas están referidas en el Vol. 1: “Fundamentos Técnicos”.


Detail X