VD/SV-AD, VD/SV-ADL

Válvula de alívio de pressão e vácuoà prova de deflagração

Features

Extreme Tightness
resulting in lowest possible product Product Includes equipment, protective systems, devices, components and combinations of these. losses and reduced environmental pollution
More Efficient Opening and Closing
valve opens later and closes earlier than conventional valves
Flow Capacity
optimized flow capacity
API Tanks
best technology for API tanks
Function and Description

combined pressure and vacuum relief valve

The deflagration Deflagration Explosion propagating at subsonic velocity (EN 1127-1:1997). proof VD/SV-AD(L) type PROTEGO® valve is a highly developed combined pressure/vacuum relief valve Pressure/vacuum relief valve Pressure/vacuum relief valve is an umbrella term that includes pressure or vacuum relief valve as well as pressure and vacuum relief valve. for high flow capacities with an integrated flame arrester unit Flame arrester unit Flame arrester casing with FLAMEFILTER® set. . It is primarily used as a device Device A device is a pipe component that influences the media flow by opening, closing, or partially shutting off the flow channel or by dividing or mixing the media flow. for flame-transmission-proof in-breathing and out-breathing in tanks, containers, and process equipment Equipment Machines, appliances, fixed or mobile devices, control parts and accessories, and warning and prevention systems, whether separate or combined, intended for the generation, transfer, storage, measurement, control, and conversion of energy, and for the processing of materials, which have their own potential source of ignition and may cause an explosion. . The valve offers reliable protection against overpressure Overpressure Overpressure refers to an increase in pressure in a system or vessel above the normal operating pressure. and vacuum Vacuum Vacuum is the pressure in an enclosed space that is lower than the ambient pressure. , prevents out-breathing of product vapor and in-breathing of air almost up to the set pressure, and protects against atmospheric deflagration. The PROTEGO® flame arrester unit is designed to achieve minimum pressure rop with maximum safety. The deflagration-proof PROTEGO® VD/SV-AD(L) valve is available for substances from explosion Explosion Abrupt oxidation or decomposition reaction producing an increase in temperature, pressure, or in both simultaneously. groups IIA to IIB3 (NEC group D to C MESG ≥ 0.65 mm).

10%-Technoglogy

When the set pressure is reached, the valve starts to open and reaches full lift within 10% overpressure. This unique 10% technology enables a set pressure that is only 10% below the maximum allowable working pressure (MAWP) or maximum allowable working vacuum (MAWV) of the tank. After years ofdevelopment, this typical opening characteristic of a safety relief valve is now also available for the low pressure range.

advanced manufacturing technology

The tank pressure Tank pressure Tank pressure is the pressure within a tank. is maintained up to the set pressure with a tightness that is above to the normal standards due to our state-of-the-art manufacturing technology. This feature is ensured by the valve seats made of high quality stainless steel and with individually lapped valve pallets (1), or with an air cushion seal Seal A seal prevents or limits unwanted transfer of product from one container to another. Seal is used as superordinate term for all types of sealing elements. (2), in conjunction with high quality FEP diaphragm Diaphragm A diaphragm is a thin layer of material, which has a large surface area. . The valve pallets are also available with a PTFE seal to prevent them from sticking when sticky substances are used and to enable the use of corrosive fluids. After the overpressure is released or the vacuum is balanced, the valve reseats and provides a tight seal.

Main component - PROTEGO® flame arrester

If the set pressure is exceeded, explosive gas/product vapor/air mixtures are released into the atmosphere. If this mixture ignites, the integrated PROTEGO® flame arrester unit (3) revents flame transmission resulting from atmospheric deflagration into the tank. The vacuum side is also protected against atmospheric deflagration. The valve can be used at an operating temperature Operating temperature Temperature reached when the equipment is operating under design conditions. of up to +60°C / 140°F and meets the requirements of European tank design standard EN 14015 (Appendix L) and ISO 28300 (API 2000). EU conformity according to the currently valid ATEX directive. Approvals according to other national/international regulations on request.
Product Data and Features

Tabela de dimensões

Para escolher o diâmetro nominal (DN), veja os diagramas de vazão nas páginas seguintes

VD / SV-AD VD / SV-ADL
DN80 / 3"100 / 4"100 / 4"150 / 6"
a540565650760
b475575700855
c350350600600

Dimensões em mm

Seleção do grupo de explosão

MESG Gr. expl. (IEC / CEN) Grupo gás (NEC)
≥ 0,65 mmIIB3C

Aprovações especiais sob solicitação

Tipo de conexão flangeada

EN 1092-1; Form B1
ASME B16.5 CL 150 R.F.

Outras conexões sob solicitação

Versão e especificação

Quase todas as faixas de pressão e vácuo da válvula podem ser combinadas livremente. Os obturadores da válvula são calibrados por peso.
Estão disponíveis duas versões:
Válvula de alívio de pressão e vácuo na versão com corpo padrãoVD/SV-AD
Válvula de alívio de pressão e vácuo na versão com corpo estendidoVD/SV-ADL

Outros dispositivos especiais sob solicitação

Ajustes de pressão

Pressão:+3.5 mbar+35 mbar
+1.4 inch W.C.+14 inch W.C.
Vácuo:-2.0 mbar-35 mbar
-0.8 inch W.C.-14 inch W.C.

Ajustes de pressão mais altos ou baixos sob solicitação

Seleção do material do corpo

Execução AB
Corpo Aço Aço inoxidável
Sedes de válvulas Aço inoxidável Aço inoxidável
VedaçãoPTFEPTFE
Tampa Aço inoxidável Aço inoxidável
Conjuntos abafadores de chamasA, BB

Os corpos também podem ser fornecidos com revestimento de ECTFE

Sonderwerkstoffe auf Anfrage

Combinações de material do conjunto abafador de chamas

Execução AB
Armação do FLAMEFILTER® Aço
Aço inoxidável
FLAMEFILTER® Aço inoxidável Aço inoxidável

Materiais especiais sob solicitação

Seleção do material do disco da válvula de pressão

Execução ABCD
Faixa de pressão [mbar]+3,5 até +5>+5,0 até +14>+14 até +35>+14 até +35
Obturador da válvula Alumínio Aço inoxidável Aço inoxidável Aço inoxidável
VedaçãoFEPFEP metálicaPTFE

Materiais especiais, bem como pressões maiores, sob solicitação

Seleção do material do disco da válvula de vácuo

Execução ABCD
Faixa de pressão [mbar]-2,0 até -3,5<-3,5 até -14<-14 até -35<-14 até -35
Obturador da válvula Alumínio Aço inoxidável Aço inoxidável Aço inoxidável
VedaçãoFEPFEP metálicaPTFE

Materiais especiais, bem como vácuos maiores, sob solicitação

Diagrama de vazão

Este diagrama de vazão foi determinado em uma bancada de medição de vazão calibrada e certificada pela TÜV. A vazão V em m³/h se refere ao estado técnico padrão de ar, conforme ISO 6358 (20°C, 1bar). Para conversão em outras densidades e temperaturas, veja o cap. 1: Bases técnicas.

Detalhe X

Detalhe X

Applications