P/EBR-E-IIB1

Válvula de alívio de pressãoà prova de deflagração e combustão contínua

Features

Extreme Tightness
resulting in lowest possible product Product Includes equipment, protective systems, devices, components and combinations of these. losses and reduced environmental pollution
Safety Against Endurance Burning
Protection against Atmospheric Deflagration and Endurance Burning
Modular Design
allows replacement and cleaning of single FLAMEFILTER®
Function and Description

Combined Pressure and Vacuum Relief Valve

The deflagration-proof and endurance burning-proof PV/EBR-E type PROTEGO® valve is a highly developed combined pressure/vacuum relief valve Pressure/vacuum relief valve Pressure/vacuum relief valve is an umbrella term that includes pressure or vacuum relief valve as well as pressure and vacuum relief valve. for high flow capacities with an integrated flame arrester that is specifically designed for use in ethanol production, processing, and storage. It is primarily used as a device Device A device is a pipe component that influences the media flow by opening, closing, or partially shutting off the flow channel or by dividing or mixing the media flow. for flame transmission-proof Flame transmission-proof Characteristic of a device to avoid flashback. out-breathing on tanks, containers, and process equipment Equipment Machines, appliances, fixed or mobile devices, control parts and accessories, and warning and prevention systems, whether separate or combined, intended for the generation, transfer, storage, measurement, control, and conversion of energy, and for the processing of materials, which have their own potential source of ignition and may cause an explosion. . The valve offers reliable protection against overpressure Overpressure Overpressure refers to an increase in pressure in a system or vessel above the normal operating pressure. and vacuum Vacuum Vacuum is the pressure in an enclosed space that is lower than the ambient pressure. , prevents the in-breathing of air and product losses almost up to the set pressure, and protects against atmospheric deflagration and endurance burning if stabilized burning Stabilized burning Steady burning of a flame stabilized at, or close to the flame arrester element. occurs.

For Explosion group IIB1

The PROTEGO® flame arrester unit is designed to achieve minimum pressure drop with maximum safety. The PROTEGO® PV/EBR-E valve is available for substances from explosion group IIB1 (MESG ≥ 0.85 mm) and provides specific protection against deflagration and endurance burning of alcohol/air mixtures (such as ethanol/air). The valve functions proportional, so the set pressures should be selected in relation to the proportional behavior (such as a 10%, 40%, or 100% overpressure from the set pressure to the relieving pressure Relieving pressure The relieving pressure is the vacuum or overpressure at which the valve reaches the lift required for the mass flow to be discharged. at which the required flow performance is reached).

Advanced manufacturing technology

The tank pressure Tank pressure Tank pressure is the pressure within a tank. is maintained up to the set pressure with a tightness that is above the normal standards due to our state-of-the-art manufacturing technology. This feature is ensured by the valve seats made of high quality stainless steel and with individually lapped valve pallets (1), or with an air cushion seal Seal A seal prevents or limits unwanted transfer of product from one container to another. Seal is used as superordinate term for all types of sealing elements. (2), in conjunction with high quality FEP diaphragm Diaphragm A diaphragm is a thin layer of material, which has a large surface area. . The valve pallets are also available with a PTFE seal to prevent the valve pallets from sticking when sticky substances are used and to enable the use corrosive fluids. After the overpressure is released, the valve re-seats and provides a tight seal.

Main component - PROTEGO® flame arrester

If the set pressure is exceeded, explosive gas/product vapor/air mixtures are released into the atmosphere. If this mixture ignites, the integrated PROTEGO® flame arrester unit (3) prevents flame transmission into the tank. If additional mixture continues to flow and stabilized burning occurs, the integrated flame arrester unit Flame arrester unit Flame arrester casing with FLAMEFILTER® set. prevents flashback Flashback Phenomenon occurring in a flammable mixture of air and gas when the local velocity of the combustible mixture becomes less than the flame velocity, causing the flame to travel back to the point of mixture. as a result of endurance burning. The valve is protected and also fulfils its function under these severe conditions. The spring Spring A spring is a spiral of wire which returns to its original shape after it is pressed or pulled. -loaded weather hood Weather hood A weather hood is a cover to protect the internal components of a device from environmental influences. opens as soon as the melting element Melting element The melting element is a component that consists of a housing with a lower and upper part. (4) melts.

Many Individual Certifications

The valve can be used at an operating temperature Operating temperature Temperature reached when the equipment is operating under design conditions. of up to +60°C / 140°F and meets the requirements of European tank design standard EN 14015 (Appendix L) and ISO 28300 (API 2000). EU conformity according to the currently valid ATEX directive. Approvals according to other national/international regulations on request.
Product Data and Features

Tabela de dimensões

Para escolher o diâmetro nominal (DN), veja o diagrama de vazão da página seguinte

DN80 / 3" 80 / 3" 100 / 4" 100 / 4"
Pressão≤ +80 mbar> +80 mbar≤ +80 mbar> +80 mbar
a353353353353
b345505345505

Dimensões em mm

Dimensões para a válvula de alívio de pressão com camisa de aquecimento sob solicitação

Seleção do grupo de explosão

MESG Gr. expl. (IEC / CEN) Grupo gás (NEC)
≥ 0,85 mmIIB1

Aprovações especiais sob solicitação

Tipo de conexão flangeada

EN 1092-1; Form B1
ASME B16.5 CL 150 R.F.

Outras conexões sob solicitação

Versão e especificação

O obturador da válvula é calibrado por peso. Com pressões de ajuste >80 mbar se utiliza um modelo estendido.
Estão disponíveis duas versões:
Válvula de alívio de pressão na versão básicaP/EBR - E - –
Válvula de alívio de pressão com camisa de aquecimento (temperatura máx. do meio de aquecimento +85°C)P/EBR - E - H

Outros dispositivos especiais sob solicitação

Settings

Pressure:+3.5 mbar+210 mbar
+1.4 inch W.C.+84 inch W.C.

Higher pressure settings upon request.

Seleção do material do corpo

Execução BC
CorpoAçoAço inoxidável
Camisa de aquecimento (P / EBR-E-H-...)AçoAço inoxidável
Sede de válvulaAço inoxidávelAço inoxidável
TampaAçoAço inoxidável

Materiais especiais sob solicitação

Combinações de material do conjunto abafador de chamas

ExecuçãoA
Armação do FLAMEFILTER®Aço inoxidável
FLAMEFILTER®Aço inoxidável
EspaçadoresAço inoxidável

Materiais especiais sob solicitação

Seleção de material do obturador da válvula

Execução         ABCD
Faixa de pressão [mbar]+3,5 até +5,0>+5,0 até +14>+14 até +210>+14 até +210
Obturador da válvulaAlumínioAço inoxidávelAço inoxidávelAço inoxidável
VedaçãoFEPFEPmetálicaPTFE

Materiais especiais e ajustes de pressão mais altos sob solicitação

Diagrama de vazão

Este diagrama de vazão foi determinado em uma bancada de medição de vazão calibrada e certificada pela TÜV. A vazão V em m³/h se refere ao estado técnico padrão de ar, conforme ISO 6358 (20°C, 1bar). Para conversão em outras densidades e temperaturas, veja o cap. 1: Bases técnicas.

Detalhe X

Detalhe X

Applications