UB/DF
Pressure Diaphragm Valvedeflagration- and endurance burning-proof

Features
Extreme Tightness
Optimal Pressure Maintenance
Flow Capacity
Protective System According to ATEX
Safety Against Endurance Burning
Safe Venting
Frost-Proof
Condensate Drainage
Monitoring
Modular Design
Suitable for challenging applications
Easy operation Monitoring

Highly Developed Pressure Relief Valve

For Explosion group IIB3

Operation of the Overpressure Relief Valves
Overpressure Protection with Advanced Sealing Technology
Dynamic Flame Arresting at Overpressure Conditions
Main component - PROTEGO® flame arrester
Many Individual Certifications
Dimensions
To select the nominal size Nominal size The nominal size is an alphanumeric designation of size for components in a piping system, used for reference purposes, comprising the letters DN followed by a dimensionless integer that is indirectly related to the physical size of the bore or outside diameter of the connections, expessed in millimeters. (DN), please use the flow capacity charts on the following pages
| DN | pressure | pressure | 80 / 3" | pressure | pressure | 100 / 4" | pressure | pressure | 150 / 6" |
| a | up to +28 mbar | up to +11.2 inch W.C. | 615 / 24.21 | up to +28 mbar | up to +11.2 inch W.C. | 645 / 25.39 | up to +25 mbar | up to +10 inch W.C. | 680 / 26.77 |
| a | > +28 mbar | > +11.2 inch W.C. | 765 / 30.12 | > +28 mbar | > +11.2 inch W.C. | 795 / 31.30 | > +25 mbar | > +10 inch W.C. | 830 / 32.68 |
| b | 410 / 16.14 | 485 / 19.09 | 590 / 23.23 |
Dimensions in mm / inches
Pressure settings > +50 mbar / +20 inch W.C. (DN 80/3”), > +45 mbar / +18 inch W.C. (DN 100/4”), > +46 mbar / +18.4 inch W.C. (DN150/6”) with additional liquid reservoir - dimensions upon request
Dimensions for pressure diaphragm valves with heating coil Heating coil A heating coil is a pipe connection consisting of several pipe sections. upon request
Selection of explosion group
| MESG | Expl. Gr. (IEC / CEN) | Gas Group (NEC) |
| ≥ 0,65 mm | IIB3 | C |
Special approvals upon request
Flange connection type
| EN 1092-1; Form B1 |
| ASME B16.5 CL 150 R.F. |
other types upon request
Design Types and Specifications
The diaphragm is pressurized by liquid. Higher pressures can be achieved upon request with a special liquid reservoir.There are two different designs:
In addition to the standard design, a series of specially developed designs, which are particularly suitable for operating conditions to which these products are subjected, can be provided upon request (for example, for acrylics or styrene storage tanks, etc.).
Settings
| DN 80 | +3.5 mbar | +50 mbar |
| +1.4 inch W.C. | +20 inch W.C. | |
| DN 100 | +3.5 mbar | +45 mbar |
| +1.4 inch W.C. | +18 inch W.C. | |
| DN 150 | +3.5 mbar | +46 mbar |
| +1.4 inch W.C. | +18.4 inch W.C. |
Higher pressure settings up to +140 mbar (56.2 inch W.C.) in special design with additional liquid reservoir as well as lower pressure settings upon request.
Material selection for housing
| Design | B | C | D |
| Housing Housing A housing is a solid shell, which surrounds a content, either protecting the content from external influences, or protecting the environment from the content. | Cast Iron | Steel | Stainless Steel |
| Valve top | Stainless Steel | Stainless Steel | Stainless Steel |
| Heating coil (UB / DF-H-...) | Stainless Steel | Stainless Steel | Stainless Steel |
| Valve seat | Stainless Steel | Stainless Steel | Stainless Steel |
| Gasket | FPM | FPM | PTFE |
| Diaphragm | A, B | A, B | A, B |
| Flame arrester unit Flame arrester unit Flame arrester casing with FLAMEFILTER® set. | A | C | C |
Option: Housing with ECTFE- lining Lining Protective plastic lining with a defined minimum/maximum thickness to protect against aggressive mixtures (e.g., acid).
Special materials upon request
Material selection
| Design | A | B |
| Diaphragm | FPM | FEP |
Special materials upon request
Material combinations of flame arrester unit
| Design | A | C |
| FLAMEFILTER® cage | Cast Iron | Stainless Steel |
| FLAMEFILTER® | Stainless Steel | Stainless Steel |
| Spacer Spacer The spacer is a component that is generally used in a PROTEGO® flame arrester as a spacer within the FLAMEFILTER® se | Stainless Steel | Stainless Steel |
Special materials upon request
Flow Capacity Chart


UB/DF DN100 Pressure


UB/DF DN150 Pressure


The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig. Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar). For conversion to other densities and temperatures refer to Sec. 1: “Technical Fundamentals”.