DV/ZT
Pressure and Vacuum Relief Valve, In-Line

Features
10% Technology
Extreme Tightness
Optimum Pressure Maintenance
High Flow Capacity
Used in Explosion Hazardous Areas
Sturdy Housing Design

Pressure or Backflow Protection in Venting or Exhaust Lines

Full Lift Technology

Custom Materials
Dimensions
To select the nominal size Nominal size The nominal size is an alphanumeric designation of size for components in a piping system, used for reference purposes, comprising the letters DN followed by a dimensionless integer that is indirectly related to the physical size of the bore or outside diameter of the connections, expessed in millimeters. (DN), please use the flow capacity chart on the following page
| DN | 40 / 1½“ | 50 / 2" | 80 / 3" | 100 / 4" | 150 / 6" |
| a | 280 / 11.02 | 280 / 11.02 | 340 / 13.39 | 390 / 15.35 | 520 / 20.47 |
| b | 270 / 10.63 | 270 / 10.63 | 290 / 11.42 | 355 / 13.98 | 425 / 16.73 |
| c | 210 / 8.27 | 210 / 8.27 | 280 / 11.02 | 310 / 12.20 | 390 / 15.35 |
Dimensions in mm / inches
Larger sizes upon request
Dimensions for pressure and vacuum relief valve with heating jacket upon request
Material selection for housing
| Design | A | B |
| Housing Housing A housing is a solid shell, which surrounds a content, either protecting the content from external influences, or protecting the environment from the content. | Steel | Stainless Steel |
| Heating jacket (DV / ZT-H-...) | Steel | Stainless Steel |
| Valve seat Valve seat The valve seat is a component on which the valve pallet rests when the valve is closed. | Stainless Steel | Stainless Steel |
| Gasket | PTFE | PTFE |
Option: Housing with ECTFE- lining Lining Protective plastic lining with a defined minimum/maximum thickness to protect against aggressive mixtures (e.g., acid).
Special materials upon request
Material selection for upper valve pallet
| Design | A | B | C | D |
| Pressure range [mbar] [inch W.C.] | ±2.0 up to ±3.5 ±0.8 up to ±1.4 | ±3.5 up to ±14 >±1.4 up to ±5.6 | ±14 up to ±60 >±5.6 up to ±24 | ±14 up to ±60 >±5.6 up to ±24 |
| Valve pallet | Aluminium | Stainless Steel | Stainless Steel | Stainless Steel |
| Sealing | FEP | FEP | Metal to Metal | PTFE |
Special materials upon request
For higher set pressure refer to type DV/ZT-F.
Material selection for lower valve pallet
| Design | A | B | C | D | E | F |
| Pressure range [mbar] [inch W.C.] | ±2,0 up to ±3,5 ±0.8 up to ±1.4 | ±3,5 up to ±14 ±1.4 up to ±5.6 | ±14 up to ±35 ±5.6 up to ±14 | ±35 up to ±50 ±14 up to ±20 | ±14 up to ±35 ±5.6 up to ±14 | ±35 up to ±50 ±14 up to ±20 |
| Valve pallet | Aluminium | Stainless Steel | Stainless Steel | Stainless Steel | Stainless Steel | Stainless Steel |
| Sealing | FEP | FEP | Metal to Metal | Metal to Metal | PTFE | PTFE |
Special materials and lower set vacuum Set vacuum Internal negative gauge pressure at which a vacuum valve first opens. upon request
Flange connection type
| EN 1092-1; Form B1 |
| ASME B16.5 CL 150 R.F. |
other types upon request
Design Types and Specifications
The valve pallets are weight loaded. Higher set pressures are achieved by using spring Spring A spring is a spiral of wire which returns to its original shape after it is pressed or pulled. loaded type DV/ZT-FTwo different designs are available:
Additional special devices available upon request
Within piping systems the influence of backpressure has to be considered in deciding the set pressure and opening characteristics. For special design solutions (e.g. partial load operation) the valve can be supplied with standard valve pallets (with proportional opening function).
Settings
| Upper valve pallet: | ±2.0 mbar | ±60 mbar |
| ±0.8 inch W.C. | ±24 inch W.C. | |
| Lower valve pallet: | ±3.5 mbar | ±50 mbar |
| ±1.4 inch W.C. | ±20 inch W.C. |
For higher set pressure refer to type DV/ZT-F.
Lower set vacuum upon request.
Flow Capacity Chart


The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig. Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar). For conversion to other densities and temperatures refer to Sec. 1: “Technical Fundamentals”.


Detail X

Detail X

Tank connection; Other arrangement of the tank connection upon request.