Features
Venting and Breathing of Floating Roof Tanks
Low position of the Floating Roof
Different Heights
Conversion
Adjustment through an adjustment option
Not flame transmission proof
Automatic Venting Valves for Floating Roof Tanks
Design of Valves
Dimensions for Different Floating Roof Heights
Conversion of Floating Roof Supports and Extension of the Plunger
Maßtabelle für AL-DK und AL-DK-4
| AL-DK | AL-DK-4 | |||||||
| DN1 | 200 / 8" | 200 / 8" | 200 / 8" | 200 / 8" | 250 / 10" | 250 / 10" | 200 / 8" | 200 / 8" |
| DN2 | 80 /3" | 100 /4" | 150 / 6" | 200 / 8" | 150 / 6" | 200 / 8" | 100 /4" | 200 / 8" |
| a | 350 / 13.78 | 350 / 13.78 | 350 / 13.78 | 350 / 13.78 | 350 / 13.78 | 350 / 13.78 | 350 / 13.78 | 350 / 13.78 |
| b | 465 / 18.31 | 465 / 18.31 | 465 / 18.31 | 515 / 20.28 | 465 / 18.31 | 515 / 20.28 | 465 / 18.31 | 650 / 25.59 |
| c | 870 / 34.25 | 870 / 34.25 | 870 / 34.25 | 870 / 34.25 | 870 / 34.25 | 870 / 34.25 | 870 / 34.25 | 870 / 34.25 |
| d | 450 / 17.72 | 450 / 17.72 | 450 / 17.72 | 450 / 17.72 | 450 / 17.72 | 450 / 17.72 | 450 / 17.72 | 600 / 23.62 |
| e | 345 / 13.58 | 360 / 14.17 | 385 / 15.16 | 415 / 16.34 | 385 / 15.16 | 415 / 16.34 | 415 / 16.34 | 415 / 16.34 |
| f | 460 / 18.11 | 445 / 17.52 | 285 / 11.22 | 370 / 14.57 | 285 / 11.22 | 367 / 14.45 | 445 / 17.52 | 370 / 14.57 |
| x | 658 / 25.91 | 920 / 36.22 | ||||||
Dimensions in mm / inches
Material
| Housing | Steel |
| Valve guide | Stainless Steel |
| Gasket | FPM |
Special materials upon request
Selection and Design
The required quantity and nominal size Nominal size The nominal size is an alphanumeric designation of size for components in a piping system, used for reference purposes, comprising the letters DN followed by a dimensionless integer that is indirectly related to the physical size of the bore or outside diameter of the connections, expessed in millimeters. DN will be defined based on the calculated flow rate from the thermal venting and pumprate in lowest floating roof position (Nm³/h or CFH) and based on the maximum acceptable tank pressure Tank pressure Tank pressure is the pressure within a tank. pT (mbar / inch W.C.) according to the flow capacity charts. Special models are available on request.Flow rates and pressure losses of vent caps PROTEGO® EB or PROTEGO® LH/AD have additionally to be taken into account according to the appropriate charts in the relevant data sheetsor operating instructions.Data Necessary for Specification
Stored product Product Includes equipment, protective systems, devices, components and combinations of these. Tank diameter (m or ft)Tank diameter (m or ft)
Tank height (m or ft)
Support height h1 (operating position with empty tank)
Support height h2 (lifted assembly position)
Maximum allowable tank pressure pT (mbar or inch W.C.)
Pump rate (m³/h or CFH)
Flange connection type
| EN 1092-1; Form B1 | andere Anschlüsse auf Anfrage |
| ASME B16.5 CL 150 R.F. |
Other types upon request
Design Types and Specifications
Two designs are available:Flow Capacity Chart
The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig. Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar). For conversion to other densities and temperatures refer to Sec. 1: “Technical Fundamentals”.
Application Examples for PROTEGO® AL-DK
Lift-actuated vent valves of type PROTEGO® AL-DK can be combined with vent caps type EB which are deflagration Deflagration Explosion propagating at subsonic velocity (EN 1127-1:1997). proof and resistant against endurance burning Endurance burning Stabilized burning for an unlimited time. . This ensures flame transmission proof ventilation.
If resistance against endurance burning is not required the valves can alternatively be combined with PROTEGO® deflagration proof devices type PROTEGO® LH/AD. The applicable data sheets are available in volume 2 “ Deflagration Flame Arresters Deflagration flame arrester Flame arrester designed to prevent the transmission of a deflagration. It can be an end-of-line flame arrester or an in-line flame arrester. , end-of-line and Vent Caps”.