P/EB

Pressure Relief Valvedeflagration- and endurance burning-proof

Features

Extreme Tightness
resulting in lowest possible product Product Includes equipment, protective systems, devices, components and combinations of these. losses and reduced environmental pollution
More Efficient Opening and Closing
valve opens later and closes earlier than conventional valves
Safety Against Endurance Burning
Protection against Atmospheric Deflagration and Endurance Burning
Modular Design
allows replacement and cleaning of single FLAMEFILTER®
Function and Description

Highly Developed Pressure Relief Valve

The deflagration Deflagration Explosion propagating at subsonic velocity (EN 1127-1:1997). -proof and endurance burning Endurance burning Stabilized burning for an unlimited time. -proof P/EB type PROTEGO® valve is a highly developed pressure relief valve Pressure-relief valve Valve designed to open and relieve excess pressure and to reclose and prevent the further flow of fluid after normal conditions have been restored. with an integrated flame arrester unit Flame arrester unit Flame arrester casing with FLAMEFILTER® set. . It is primarily used as a device Device A device is a pipe component that influences the media flow by opening, closing, or partially shutting off the flow channel or by dividing or mixing the media flow. for flame transmission-proof Flame transmission-proof Characteristic of a device to avoid flashback. out-breathing on tanks, containers, and process equipment Equipment Machines, appliances, fixed or mobile devices, control parts and accessories, and warning and prevention systems, whether separate or combined, intended for the generation, transfer, storage, measurement, control, and conversion of energy, and for the processing of materials, which have their own potential source of ignition and may cause an explosion. . The valve offers reliable protection against overpressure Overpressure Overpressure refers to an increase in pressure in a system or vessel above the normal operating pressure. and prevents product losses almost up to the set pressure, while at the same time protecting against atmospheric deflagration as well as endurance burning. The PROTEGO® flame arrester unit is designed to achieve minimum pressure losses with maximum safety. The PROTEGO® P/EB valve is available for substances in explosion Explosion Abrupt oxidation or decomposition reaction producing an increase in temperature, pressure, or in both simultaneously. group IIA (NEC group D MESG > 0.90 mm).

10%-Technology

When the set pressure is reached, the valve starts to open and reaches full lift within 10% overpressure. This unique 10% technology enables a set pressure that is only 10% below the maximum allowable working pressure (MAWP) of the tank. After years of development, this typical opening characteristic of a safety relief valve is now also available for the low pressure range. The tank pressure Tank pressure Tank pressure is the pressure within a tank. is maintained up to the set pressure with a tightness that is far above the normal standards due to our state-of-the-art manufacturing technology.

Custom Materials

This feature isensured by the valve seats made of high quality stainless steel and with individually lapped valve pallets (1), or with an air cushion seal Seal A seal prevents or limits unwanted transfer of product from one container to another. Seal is used as superordinate term for all types of sealing elements. (2), in conjunction with a high quality FEP diaphragm Diaphragm A diaphragm is a thin layer of material, which has a large surface area. . The valve pallets are also available with a PTFE seal to prevent them from sticking when sticky substances are used and to enable the use in corrosive fluids. After the overpressure is released, the valve re-seats and provides a tight seal.

Main component - PROTEGO® flame arrester

If the set pressure is exceeded, explosive gas/product vapor/air mixtures are released into the atmosphere. If this mixture ignites, the integrated PROTEGO® flame arrester unit (3) prevents flame transmission into the tank. If additional mixture continues to flow in and stabilized burning Stabilized burning Steady burning of a flame stabilized at, or close to the flame arrester element. occurs, the integrated flame arrester unit prevents flashback Flashback Phenomenon occurring in a flammable mixture of air and gas when the local velocity of the combustible mixture becomes less than the flame velocity, causing the flame to travel back to the point of mixture. as a result of endurance burning. The valve is protected and also fulfils its function under these severe conditions. The spring Spring A spring is a spiral of wire which returns to its original shape after it is pressed or pulled. -loaded weather hood Weather hood A weather hood is a cover to protect the internal components of a device from environmental influences. opens as soon as the melting element Melting element The melting element is a component that consists of a housing with a lower and upper part. (4) melts.

Many Individual Certifications

The valve can be used at an operating temperature Operating temperature Temperature reached when the equipment is operating under design conditions. of up to +60°C / 140°F and meets the requirements of European tank design standard EN 14015 (Appendix L) and ISO 28300 (API 2000). EU conformity according to the currently valid ATEX directive. Approvals according to other national/international regulations on request.
Product Data and Features

Dimensions

To select the nominal size Nominal size The nominal size is an alphanumeric designation of size for components in a piping system, used for reference purposes, comprising the letters DN followed by a dimensionless integer that is indirectly related to the physical size of the bore or outside diameter of the connections, expessed in millimeters. (DN), please use the flow capacity chart on the following page

DN 50 / 2" 50 / 2" 80 / 3"80 / 3"
Set pressure≤ +80 mbar> +80 mbar≤ +80 mbar> +80 mbar
Set pressure≤ +32.1 inch W.C.> +32.1 inch W.C.≤ +32.1 inch W.C.> +32.1 inch W.C.
a218 / 8.58218 / 8.58218 / 8.58218 / 8.58
b287 / 11.30452 / 17.80289 / 11.38454 / 17.87

Dimensions in mm / inches

Dimensions for Pressure Relief Valve with heating jacket upon request

Selection of explosion group

MESGExpl. Gr. (IEC / CEN)Gas Group (NEC)
> 0,90 mmIIAD

Special approvals upon request

Flange connection type

EN 1092-1; Form B1
ASME B16.5 CL 150 R.F.

other types upon request

Design Types and Specifications

The valve disc is weight-loaded. At set pressure >80 mbar (32.1 inch W.C.), an elongated design is used
There are two different designs:
Pressure relief valve, basic designP/EB - –
Pressure relief valve with heating jacket (max. heating fluid temperature +85°C / 185°F)P/EB - H

Additional special devices available upon request

Settings

Pressure:+3.5 mbar+210 mbar
+1.4 inch W.C.+84 inch W.C.

Higher pressure settings upon request.

Material selection for housing

Design
BC
HousingSteelStainless Steel
Heating jacket (P / EB-H-...)SteelStainless Steel
Valve seat Valve seat The valve seat is a component on which the valve pallet rests when the valve is closed. Stainless SteelStainless Steel
Weather hoodSteelStainless Steel

Special materials upon request

Material combinations of flame arrester unit

Special materials upon request

Material selection for valve pallet

Design  ABCD
Pressure range [mbar]
[inch W.C.]
+3.5 up to +5.0
+1.4 up to +2.0
>+5.0 up to +14
>+2.0 up to +5.6
>+14 up to +210
>+5.6 up to +84
>+14 up to +210
>+5.6 up to +84
Valve palletAluminiumStainless SteelStainless SteelStainless Steel
SealingFEPFEPMetal to MetalPTFE

Special materials and higher pressure settings upon request

Flow Capacity Chart

The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig. Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar). For conversion to other densities and temperatures refer to Sec. 1: “Technical Fundamentals”.

Detail X

Detail X

Applications