DR/EU

In-Line Detonation Flame Arrester for unstable and stable detonations and deflagrations in right angle design with a shock absorber, unidirectional

Features

Reduced Number of FLAMEFILTER® Discs
Low Number of FLAMEFILTER® Discs Due to Shock Absorber Technology
Fastest Disassembly and Assembly
of Single FLAMEFILTER®
Modular Design
Allows Replacement and Cleaning of Single FLAMEFILTER®
Angle Bodied
Saves Pipe Elbows
Spare Parts
Cost-Effective Spare Parts
Provides Safety
Protects Against Deflagrations for All Explosion Groups IIA, IIB3 and IIC (NEC Groups D, C and B)
Extended Application Range
for Elevated Operating Temperatures and Pressures
Low Costs
Low Operating and Lifecycle Costs
Function and Description

Many Individual Certifications

The standard design can be used with an operating temperature Operating temperature Temperature reached when the equipment is operating under design conditions. of up to +60°C / 140°F and an absolute operating pressure Operating pressure Operating pressure is the pressure existing at normal operating conditions within the system being protected. acc. to table 3. Devices with special approval for higher pressures and temperatures are available upon request. EU conformity according to the currently valid ATEX directive. Approvals according to other national/international regulations on request.
Product Data

Dimensions

To select the nominal size Nominal size The nominal size is an alphanumeric designation of size for components in a piping system, used for reference purposes, comprising the letters DN followed by a dimensionless integer that is indirectly related to the physical size of the bore or outside diameter of the connections, expessed in millimeters. (DN), please use the flow capacity charts on the following pages

DN25 / 1"32 / 1¼“40 / 1½“50 / 2“65 / 2½“80 / 3"100 / 4"125 / 5"150 / 6"
a125 / 4.92125 / 4.92153 / 6.02155 / 6.10198 / 7.80200 / 7.87250 / 9.84332 / 13.07335 / 13.19
b140 / 5.51140 / 5.51183 / 7.20185 / 7.28223 / 8.78225 / 8.86290 / 11.42357 / 14.06360 / 14.17
c210 / 8.27210 / 8.27290 / 11.42290 / 11.42365 / 14.37365 / 14.37440 / 17.32535 / 21.06535 / 21.06
c1285 / 11.22285 / 11.22395 / 15.55395 / 15.55500 / 19.69500 / 19.69595 / 23.43750 / 29.53750 / 29.53
d150 / 5.91150 / 5.91210 / 8.27210 / 8.27275 / 10.83275 / 10.83325 / 12.80460 / 18.11460 / 18.11
e495 / 19.49495 / 19.49600 / 23.62600 / 23.62705 / 27.76705 / 27.76795 / 31.30950 / 37.40950 / 37.40

Dimensions in mm / inches

Selection of explosion group

MESGExpl. Gr. (IEC / CEN)Gas Group (NEC)
> 0,90 mmIIAD
≥ 0,65 mmIIB3C

Special approvals upon request

Selection of max. operating pressure

Expl. Gr.DN25  / 1"32  / 1¼"40  / 1½"50 / 2"65 / 2½"80 / 3"100  / 4"125  / 5"150  / 6"
IIAPmax1,6 / 23.31,6 / 23.31,6 / 23.31,6 / 23.31,6 / 23,.31,6 / 23.31,5 / 21.71,2 / 17.41,2 / 17.4
IIB2Pmax1,4 / 20.31,4 / 20.3
IIB3Pmax1,6 / 23.21,6 / 23.31,6 / 23.31,6 / 23.31,6 / 23.31,6 / 23.31,4 / 20.31,2* / 17.41,2* / 17.4

Pmax = maximum allowable operating pressure in bar / psi absolute, higher operating pressure upon request, * Special flame arrester unit

Specification of max. operating temperature

≤ 60°C / 140°FTmaximum allowable operating temperature in °C
-Designation

higher operating temperatures upon request

Material selection for housing

Design  BCD 
Housing Housing A housing is a solid shell, which surrounds a content, either protecting the content from external influences, or protecting the environment from the content. Carbon SteelStainless SteelHastelloy
Heating jacket (DR / EU-H-(T)-...)SteelStainless SteelStainless Steel
Cover with shock absorberSteelStainless SteelHastelloy
O-RingFPM*PTFEPTFE
Flame arrester unit Flame arrester unit Flame arrester casing with FLAMEFILTER® set. AC, DESpecial materials upon request

* for devices exposed to elevated temperatures above 150°C / 302°F (T150), gaskets made of PTFE.

The housing and cover with the shock absorber can also be delivered in steel with an ECTFE coating Coating Coating is the application of a firmly adhering layer of shapeless material to the surface of a workpiece. .

Material combinations of flame arrester unit

Design ACDE
FLAMEFILTER® cageSteelStainless SteelStainless SteelHastelloy
FLAMEFILTER®*Stainless SteelStainless SteelHastelloyHastelloy
Spacer Spacer The spacer is a component that is generally used in a PROTEGO® flame arrester as a spacer within the FLAMEFILTER® set. Stainless SteelStainless SteelHastelloyHastelloy

* the FLAMEFILTER® are also available in the materials Tantalum, Inconel, Copper, etc. when the listed housing and cage materials are used.

Special materials upon request

Flange connection type

EN 1092-1; Form B1
ASME B16.5 CL 150 R.F.

Flow Capacity Chart

The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig. Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar). For conversion to other densities and temperatures refer to Sec. 1: “Technical Fundamentals”.

Applications

Installations de transformation

Systèmes de combustion de vapeur

Stockage basse-pression

 Stockage d'alcool